Blog

How do you test whether lighting can withstand the temperatures in your installation?

To test whether lighting can withstand the temperatures in your installation, compare the ambient temperature with the Ta value (maximum ambient temperature) and the Tc value (maximum temperature at the measuring point on the housing) from the luminaire’s datasheet. If the actual temperatures exceed these limits, the luminaire is not suitable for that location.

This is especially relevant in environments such as steelworks, climate chambers, chemical plants or other industrial sites where temperatures fall far outside the standard range. The sections below cover the most frequently asked questions about the temperature resistance of industrial LED lighting, from reading datasheets to choosing the right certification.

Which temperature ranges are dangerous for standard LED luminaires?

Standard LED luminaires are generally designed for ambient temperatures between -20°C and +40°C. Outside this range, the lifetime of the LED driver and the light source drops quickly. At temperatures above +40°C, the junction temperature of the LED chip rises, leading to light degradation, colour shift and, in extreme cases, premature driver failure.

A similar risk applies at the cold end. Below -20°C, capacitors in the driver can be damaged and the housing can become brittle due to thermal contraction. In climate chambers or outdoor locations in northern regions, this is a real problem that cannot be solved safely with standard products.

Environments with fluctuating temperatures are particularly treacherous, such as loading docks, production areas next to furnaces, or installations close to heat sources. Thermal cycles attack seals and increase the risk of moisture ingress. In precisely those situations it is essential to look not only at the maximum temperature, but also at the temperature difference a luminaire regularly has to withstand.

What do IP rating and IK rating say about temperature resistance?

IP rating and IK rating say nothing about temperature resistance. The IP and IK rating describe the protection against dust and moisture and the mechanical impact resistance of a luminaire respectively. A luminaire with IP66 is waterproof and dust-tight, but that does not guarantee it can withstand high or low ambient temperatures.

The confusion arises because IP rating and temperature resistance both fall under the heading “robustness”, but they measure fundamentally different properties. A luminaire can have an excellent IP rating and still fail at +60°C because the driver was not designed for that temperature.

You will find temperature information in the technical specifications of the datasheet, not in the IP or IK code. Look there specifically for the Ta value (ambient temperature) and, where applicable, the Tc value for the housing temperature. Only those values tell you whether a luminaire is suitable for your specific environment.

How do you read the temperature specifications in a luminaire datasheet?

In een armatuur datasheet zijn de temperatuurspecificaties te vinden onder benamingen als “operating temperature range”, “ambient temperature (Ta)” of “case temperature (Tc)”. De Ta-waarde geeft de maximaal toegestane omgevingstemperatuur aan. De Tc-waarde beschrijft de maximale temperatuur op een specifiek meetpunt op de behuizing, wat fabrikanten gebruiken om de thermische belasting van de driver te bewaken.

When reading a datasheet, pay attention to the following points:

  • Ta value: the maximum ambient temperature at which the luminaire may operate at full power
  • Tc value: the maximum temperature at the measuring point (Tc point) on the housing, relevant for the lifetime of the driver
  • L70 value: the number of burning hours after which the light output has dropped to 70%, strongly dependent on the operating temperature
  • Minimum ambient temperature: often forgotten, but crucial for cold environments
  • Derating information: some luminaires may only operate at reduced power at higher temperatures

A practical rule of thumb: make sure the actual ambient temperature stays at least 10°C below the stated Ta value. That gives enough margin for heat build-up by the luminaire itself and for unexpected temperature peaks in the installation.

Which test methods determine whether a luminaire can handle extreme temperatures?

Whether a luminaire can handle extreme temperatures is determined by thermal tests in which the product is exposed to the limits of its specifications under controlled conditions. The most commonly used methods are climate chamber tests, thermal cycling tests and accelerated ageing tests.

A climate chamber test simulates the actual ambient temperature over a longer period. It measures whether the driver remains stable, whether the light output is constant and whether the housing shows any deformation. In thermal cycling tests, the luminaire is repeatedly exposed to changing temperatures to test the resistance of seals, cable entries and housing joints.

In addition to these lab tests, field validation is valuable. A luminaire that has functioned successfully in a steelworks or climate chamber gives more certainty than a certified test report alone. If in doubt, ask the manufacturer for reference projects in comparable environments. That is often the most direct way to judge whether a product can cope in practice.

The following steps help you assess test results:

  1. Request the test report and check at which ambient temperature the test was carried out
  2. Compare the test temperature with the actual temperature in your installation
  3. Check whether thermal cycling tests have been carried out if your environment has temperature fluctuations
  4. Ask for L70 lifetime data measured at the relevant temperature, not just at 25°C
  5. Ask for reference projects in comparable environments as additional validation

What is the difference between high-temperature luminaires and standard industrial luminaires?

High-temperature luminaires are designed specifically for environments above +50°C to +60°C, with adapted drivers, heat-resistant materials and special cooling designs. Standard industrial luminaires are more robust than consumer products, but are generally not designed for structural exposure to extreme heat or infrared radiation.

The difference lies in several technical choices at once. High-temperature luminaires use drivers selected for performance at high ambient temperatures, not just at the standard 25°C test condition. The housing is often made of materials that do not deform under prolonged heat exposure, and the seals withstand thermal contraction and expansion.

Another important difference is protection against infrared radiation. In steelworks or near melting furnaces, the environment radiates heat not only through the air, but also directly via infrared radiation onto the luminaire housing. Standard luminaires are not designed for this. High-temperature lighting requires specific reflective or insulating measures to protect the internal components.

When is ATEX certification mandatory in addition to temperature resistance?

ATEX certification is mandatory when lighting is installed in a space where explosive atmospheres can arise from gases, vapours, mists or dust particles. This applies regardless of whether extreme temperatures are also present. Temperature resistance and ATEX are two separate requirements that may both apply.

In practice, both requirements occur together in environments such as chemical plants, refineries, offshore installations and certain parts of mining. A luminaire in such an environment must both withstand the actual ambient temperature and be certified for use in a potentially explosive zone. An ATEX-certified luminaire that is not designed for high ambient temperatures then only meets half of the requirements.

Within ATEX certification, temperature also plays a role of its own: luminaires are assigned a temperature class (T1 to T6) that indicates the maximum surface temperature of the luminaire. That value must be lower than the ignition temperature of the substances present. So in ATEX applications it is important to check both the ambient temperature and the temperature class of the luminaire.

Practical example: VPK Paper

In VPK Paper’s paper mills in Belgium, the temperature in and around the paper machine rises to +120 °C in the most extreme cases, with steam and very high humidity in the machine itself. None of the LED solutions tried earlier had held up. VPK Paper therefore opted for proof in advance: first a trial with the Snapper HT under the real conditions, and only then the roll-out. That trial succeeded. JEL took care of the lighting design and engineering, designed the installation and supplied 98 Snapper HT in AC version, good for 100 to 200 lux in the machine at 35 W per luminaire.

A datasheet tells you what a luminaire does under test conditions, but the combination of heat, steam and moisture in a running machine is difficult to replicate. A trial on your own site closes that gap. What counts is not only whether the luminaire gives light in the first weeks, but also whether the seal keeps moisture out permanently, because moisture finds every weak spot.

Read more about the VPK Paper project

How JEL Products helps with the temperature resistance of lighting

JEL Products supports companies in selecting and implementing lighting that matches the actual conditions in their installation. That starts with a thorough analysis of the environment, not with a catalogue.

  • Custom technical advice: JEL Products maps the temperature conditions in your installation and links them to the right luminaire specifications
  • High-temperature luminaires the Orca HT and Barracuda HT floodlights have been developed specifically for environments up to +120°C, including protection against infrared radiation
  • Climate chamber lighting: for cold environments down to -45°C, JEL Products supplies luminaires that function reliably even in extreme cold
  • Lighting outside the ATEX zones: for the parts of the site outside potentially explosive zones, with referral to a certified Ex manufacturer for the zones themselves
  • Full project management: from lighting design and engineering to installation and commissioning
  • ISO9001 and VCA** certified: quality assurance throughout the entire process

Would you like to know which lighting is suitable for the temperatures in your installation? Get in touch with JEL Products for a technical conversation without obligation.